An inlet breeching at ground level provides the connection to the water supply. The system is normally dry and is charged
by the fire brigade in an emergency. Breeching inlets have either 2 or 4 inlet connections complete with 2.5” male instantaneous
inlets to BS336 fitted with non-return valves, 1” drain valve and caps and chains. A 100mm (4”) rising main uses a 2-way
inlet breeching in a vertical or horizontal position. A 150mm (6”) rising main uses a 4-Way inlet breeching. Inlet Breechings
comply with the requirements of BS 5041 Part 3

 

The Breechings are normally housed in inlet cabinets, normally recessed into the external wall of the building in a vertical
or horizontal position, 4 -way breechings in a square inlet breeching cabinet, manufactured in accordance with BS 5041 Part
5. Cabinets for foam inlets are available on request.

 

   4-Way Breeching Inlet Cabinet

1

1

Elite 1804 Red Ral 3002 As Standard
Elite 2030 Stainless Steel Satin Polished
(See Cabinet Options)
Backbox Dimensions
595mm High x 595mm Wide x 295mm Deep

 

    (Minimum aperture 605mm wide 605mm high)

Cabinet Specifications:


Cabinet & Door: 16swg Zintec Steel.
Colour: As Standard Red Ral 3002.
Architrave: 30mm Wide All Round.
Glass: 6mm Georgian Wired, PRV Lettering.
Lock: Yale Slam Lock Keyed Alike.
Hinge: Stainless Steel Piano Hinge.

Conforms: To BS 5041 Part 5

 

4-Way Breeching Inlet Valve

1

Elite 012 Outlet Flanged 150mm
BS 4504 PN16

1